An
ERV (energy recovery ventilator) is a balanced supply-and-exhaust ventilator with an enthalpy core: it transfers not only heat but also part of the water vapor between the two air streams.
To size an ERV correctly, you need to work out the required airflow based on the floor area of your home (CFM per square foot) and the number of bedrooms. The ASHRAE 62.2 method is the standard way to do this. Below you will find a quick rule of thumb, the full calculation with an example, and a sizing table you can use as a CFM calculator.
Quick Answer: CFM per Square Foot Rule of Thumb
A widely used rule of thumb for a first estimate is 0.05 CFM per square foot of floor area, or 5 CFM for every 100 sq ft. For example, a 1,500 sq ft home needs about 75 CFM, a 2,000 sq ft home about 100 CFM, and a 3,000 sq ft home about 150 CFM.
Keep in mind that sizing by floor area gives only a preliminary estimate. For the final ERV selection, you also need to account for the number of bedrooms, the required ventilation rate and the characteristics of the duct system.
CFM (cubic feet per minute) is the unit used to measure ventilation airflow: the volume of air that moves through the system in one minute.
How to Size an ERV: The ASHRAE 62.2 Method
ASHRAE 62.2 is the US standard that sets minimum ventilation and indoor air quality requirements for residential buildings. Unlike the simplified floor-area estimate, this method also takes the number of bedrooms into account, which reflects the expected number of occupants and gives a more accurate picture of how much fresh air the home needs.
The standard is updated regularly; the current edition is ASHRAE 62.2-2025.
The total required ventilation rate (ASHRAE 62.2 ventilation rate) is calculated with this formula:
Q = 0.03 × A + 7.5 × (N + 1), where:
- Q is the required airflow, CFM;
- A is the conditioned floor area of the home, sq ft;
- N is the number of bedrooms (use at least one).
CFM Calculation Example
Let's say the home is 2,000 sq ft and has three bedrooms. Plug in the values:
- Q = 0.03 × 2,000 + 7.5 × (3 + 1) = 60 + 30 = 90 CFM.
So the home needs 90 CFM of continuous ventilation. That is the baseline ERV CFM requirement to use when selecting a unit.